Lighting power density:
watts of lighting per square metre of floor
One ratio, installed watts over floor area, lets you compare a small office with a warehouse and check a design against an energy code.
Calcylator Editorial Team
Updated · 4 min read
What the ratio captures
Lighting power density, often shortened to LPD, is the installed lighting load spread over the floor area it serves. It tells you how electrically hungry a lighting scheme is per square metre, independent of the room's size, so a design for a small studio and one for a large open-plan floor can be put side by side.
Energy codes and green-building schemes often set limits in W/m² for different space types, and designers use LPD during design to show compliance. The limits, and the way the area and the watts are counted, differ between regions and standards, so use the one that applies to your project.
It is a measure of connected power, not of actual energy use or of how bright the room is. Two rooms with the same LPD can use very different energy if one is lit for 12 hours and the other for 2.
The calculation step by step
- P:
- total installed lighting power, W (include driver and ballast losses)
- A:
- floor area of the space, m²
Fixtures
20 × 24 W = 480 W
Floor area
80 m²
Lighting power density
6 W/m²
480 ÷ 80 = 6 W/m². Doubling the fixtures with the same area would give 12 W/m².
- List every luminaire in the space and its input power from the datasheet.
- Sum the watts, including control gear.
- Measure the floor area of the same space, excluding areas served by different circuits.
- Divide watts by area and compare with the target.
What goes into the watts and the area
The two inputs look simple, but the way they are counted changes the result. For the power, use the input power of the whole luminaire, including the driver or ballast, because a lamp marked 18 W may draw 21 W at the wall. For the area, use the floor area of the lit space, measured within the walls, and not the gross area including thick partitions or neighbouring rooms.
- Emergency and exit lighting are often counted separately; check the rule for your scheme.
- Decorative and display lighting may have an allowance of their own under some codes.
- A space that is partly open, such as a mezzanine, needs a clear boundary for the area.
- Where one circuit serves several rooms, split its load by the number of fittings in each.
Writing down how the watts and the area were measured makes a later check or a retrofit comparison much easier, and avoids arguments about whether two figures are like for like.
Comparing different spaces
The ratio becomes meaningful when you compare several rooms. The table below shows how a few typical spaces might look. These are worked illustrations of the arithmetic, not limits.
| Space | Installed watts | Area | LPD |
|---|---|---|---|
| Open office | 480 W | 80 m² | 6.0 W/m² |
| Corridor | 200 W | 20 m² | 10.0 W/m² |
| Meeting room | 144 W | 24 m² | 6.0 W/m² |
| Storage room | 90 W | 60 m² | 1.5 W/m² |
A corridor may show a high LPD simply because it is narrow and long, with few square metres per fixture. Codes recognise this by setting different limits for different space types, so a fair check compares each space with its own category rather than with the building average.
How LPD relates to light level
Power is not light. The light delivered to the work plane, measured in lux, depends on the lumens produced per watt of the source, the fraction that actually reaches the plane, and how the light has been maintained. A more efficient source needs fewer watts for the same lux.
LPD
6 W/m²
Luminaire efficacy
100 lm/W
Utilisation and maintenance factor
0.6
Approximate illuminance
360 lux
6 × 100 = 600 lm/m²; × 0.6 = 360 lux. A 500 lux target would need about 8.3 W/m² under the same factors.
This shows why LPD limits fall as lamp efficacy improves. Replacing 50 lm/W fittings with 100 lm/W units halves the watts needed for the same lux, and it is the reason retrofits can meet both the light level and the energy limit at once.
A retrofit comparison
LPD is a convenient way to show the effect of a retrofit. Imagine the same 80 m² room, first with 40 W fluorescent fittings and then with LED panels of 24 W giving similar output.
| Scheme | Fittings | Power each | Total | LPD |
|---|---|---|---|---|
| Existing fluorescent | 20 | 40 W | 800 W | 10.0 W/m² |
| LED retrofit | 20 | 24 W | 480 W | 6.0 W/m² |
| LED with dimming to 70% on average | 20 | 24 W | 336 W average | 4.2 W/m² |
The first change cuts connected power by 40% and the second reduces the average load by a further 30%, though the dimmed figure is an average in use, not connected load, so it will not count for code compliance the way the connected value does.
Old connected load
800 W
New connected load
480 W
Area
80 m²
Reduction in LPD
4 W/m²
10.0 − 6.0 = 4.0 W/m², which is a 40% reduction in connected lighting power density.
Bringing a high figure down
If a space exceeds its target, the options are to reduce the watts while keeping the light, or to reduce the light where it is not needed. The first is usually the better path.
- Switch to higher-efficacy sources and efficient drivers.
- Use task lighting at desks and lower ambient levels in the rest of the room.
- Choose luminaires with good optical control, so more of the output reaches the work plane.
- Use controls such as daylight dimming and occupancy sensing; they cut energy use even where they do not change connected load.
- Light-coloured finishes bounce more light and may allow fewer fittings.
A lighting power calculation that totals the fixture wattage of a room gives the numerator of this ratio, so it is a handy companion step, with the area as the other half. Remember to count the whole control-gear load when comparing with a code.
Common questions
How do I calculate lighting power density?
Add up the installed power of all luminaires in the space, including drivers or ballasts, and divide by the floor area in square metres. For 480 W over 80 m², the result is 6 W/m². Compare it with the limit that applies.
What is a good lighting power density?
There is no single good number, because acceptable limits depend on the space type, local energy code and light level required. A storage room may be about 1.5 W/m² while a corridor can reach 10 W/m². Check the code that governs the project.
Does lower LPD mean dimmer light?
Not necessarily. More efficient sources deliver the same lux with fewer watts. At 100 lm/W and a 0.6 factor, 6 W/m² gives about 360 lux, while 50 lm/W would need 12 W/m² for the same light level.
Is lighting power density the same as energy use?
No. LPD is connected power in W/m². Energy is power times hours of use. Two rooms at 6 W/m² differ greatly if one is lit 12 hours a day and the other only 2, so controls and operating hours matter too.
Was this guide helpful?
Continue reading
View all blogsTransformer kVA: Apparent Power from Volts and Amps
Single-phase apparent power in kVA = volts × amps ÷ 1,000. At 230 V and 20 A the load is 4.6 kVA, which is 92% of a 5 kVA transformer.
5 min read
Three-Phase Apparent Power: the √3 Formula
Three-phase apparent power in kVA = √3 × line voltage × line current ÷ 1,000. At 400 V and 25 A, a balanced load is about 17.32 kVA.
5 min read
Wire Resistance from Resistivity, Length and Area
Resistance R = ρ × L ÷ A. A 20 m copper run of 2.5 mm² (ρ = 0.0175 Ω·mm²/m) measures 0.14 Ω one way, or 0.28 Ω there and back.
5 min read




